P445E Zone Group #15 Options B Default 0
P446E Zone Group #16 Options B Default 0
P447E Zone Group #17 Options B Default 0
P448E Zone Group #18 Options B Default 0
P448E Zone Group #19 Options B Default 0
P450E Zone Group #20 Options B Default 0
Option 1 24 Hour Zone - A zone with this option turned on is active at all times and will trigger a 24 hour alarm
when activated. If the zone group has an entry delay programmed, the zone has to be in alarm for longer
than the delay time to cause an alarm. 24 Hour alarms are not assigned to areas and so are common to
all areas. Any User can reset a 24 Hour alarm.
Option 2 24 Hour Fire Zone - A zone with this option turned on is active at all times and will trigger a 24 hour fire
alarm when activated. A 24 Hour Fire zone will cause any programmed alarm outputs to pulse on & off
to differentiate it from a normal 24 hour alarm. The same entry delay function applies as per Option 1
above. 24 Hour alarms are not assigned to areas and so are common to all areas. Any User can reset a
24 Hour alarm
Option 3 24 Hour Auto-reset Zone - A zone with this option turned on is active at all times and will trigger a 24
hour alarm when activated. Unlike the other two options above, when the detector resets, the alarm will
also reset automatically without having to use a code to reset the alarm. The same entry delay function
applies as per Option 1 above. 24 Hour alarms are not assigned to areas and so are common to all
areas. Any User can reset a 24 Hour alarm
Option 4 Is a Permanent Chime Zone - A zone with this option turned on is always going to be a chime zone. It
will only ever operate the chime alarms and will never trigger a normal alarm when Armed.
Option 5 Is a Handover Zone - A zone with this option turned on will have an entry delay (a suitable delay time
must also be programmed for the same group) provided another zone (that is NOT programmed as a
handover zone) has started an entry delay. If no entry delay is active when this zone is triggered it will
act as an instant zone.
Option 6 Is a Two Trigger Zone - A zone with this option turned on must be triggered twice within the two
trigger time period (P989E) before it will cause an alarm. Alternatively, two separate zones both with the
two trigger function can alarm once each within the two trigger time period and this will also result in an
alarm. In the case of a reed switch or similar device, if a single two trigger zone is left unsealed for a
period exceeding the two trigger period this will also cause an alarm. NOTE: NEVER assign this option
to a wireless PIR or reed switch as it will not trigger an alarm when armed.
Option 7 Can Arm if zone is not “Ready” - If the Area/s assigned to this group are NOT allowed to arm if a
zone is unsealed (Not Ready) at the time of arming (see P670E, P770E, P870E & P970E option 1) then
this option will allow individual zone groups to still allow arming if a zone is unsealed.
Option 8 Is a Siren Lockout zone - A zone with this option turned on will operate any programmed outputs when
in alarm but it cannot cause another alarm (Lockout) until the area is Disarmed then Armed again. This
feature is designed to stop a zone from being able to cause multiple triggers to audible alarms.
ZONE GROUP OPTIONS C - SPECIAL FUNCTIONS
Zone Options C
P451E Zone Group #1 Options C Default 1 1 = Send Multiple reports via dialler
P452E Zone Group #2 Options C Default 1 2 = Sensorwatch Zone
P453E Zone Group #3 Options C Default 1 3 = Zone is in Soak-test Mode
P454E Zone Group #4 Options C Default 1 4 = Spare
P455E Zone Group #5 Options C Default 1 5 = Spare
P456E Zone Group #6 Options C Default 1 6 = Spare
P457E Zone Group #7 Options C Default 1 7 = Spare
P458E Zone Group #8 Options C Default 1 8 = Use second supervise timer # 2
P459E Zone Group #9 Options C Default 1
P460E Zone Group #10 Options C Default 1
P461E Zone Group #11 Options C Default 1
P462E Zone Group #12 Options C Default 1
P463E Zone Group #13 Options C Default 1
P464E Zone Group #14 Options C Default 1
P465E Zone Group #15 Options C Default 1
P466E Zone Group #16 Options C Default 1